P40 single crystal silicon differential pressure transmitter

P40 single crystal silicon differential pressure transmitter
P40 single crystal silicon differential pressure transmitter
  • Detail

Overview

The P40 series intelligent single-crystal silicon differential pressure transmitter is made with the advanced MEMS technology from Germany, featuring a unique single-crystal silicon dual-beam suspended design. It achieves world-leading high accuracy, ultra-high overpressure performance and excellent stability. With an embedded German signal processing module, it perfectly combines static pressure and temperature compensation, providing extremely high measurement accuracy and long-term stability under a wide range of static pressure and temperature variations. It is widely used in the oil, petrochemical, chemical industries and with throttling devices, offering precise flow measurement and control, as well as accurate measurement of pressure and liquid level in pipelines and storage tanks.

The P4O intelligent single-crystal silicon differential pressure (flow) transmitter can accurately measure differential pressure and convert it into a 4..2OmA DC output signal. This transmitter can be locally operated via three buttons, or configured and displayed using a universal HART hand-held communicator or configuration software, without affecting the 4.20mA output signal.


Product features

  • Outstanding overvoltage performance;

  • The working static pressure can reach up to 40 MPa.

  • High stability: 0.1%/ 60 months;

  • Excellent static pressure performance: 土0.05% of range/10 MPa;

  • High accuracy: 0.05% Comprehensive accuracy: 0.075%

  • Strong anti-interference performance;

  • Range compression ratio: 50:1;

  • Output: 4~2OmA HART/RS485;

  • Excellent environmental adaptability, with intelligent static pressure compensation and temperature compensation, ensures that the transmitter is not affected by temperature, static pressure or overpressure, minimizing the comprehensive measurement error on site.


Technical parameters

Functional Specifications

Types of stressgauge pressure, absolute pressure, differential pressure
Range of measurement1KPa... 40 MPa (for details, see the measurement range table)
Output signal4...20mA, intelligent type with HART communication protocol and RS485 communication.
The interface can provide other output signals as per customer requirements.
Load (Ω)Current output (two-wire system): mA ≤ (Power supply - 10V) / 0.02A
Voltage output (three-wire system): > Maximum output signal / 1mA
accuracy level±0.075% of full scale, maximum ±0.5% of full scale
Based on the standards and test reference conditions, the reference accuracy includes linearity, Lagging, repetitive. Calibration conditions: temperature 20 ± 5°C, atmosphere
(At a pressure of one atmosphere, which is the local atmospheric pressure)
Measured mediumFluid media such as liquids and gases that are compatible with the contact material


Measurement range table

Nominal rangeMinimum rangeLower limit of rangeUpper limit of rangeUpper limit of pressure resistance
6kPa1kPa-6kPa6kPa25MPa
40kPa2kPa-40kPa40kPa25MPa
250kPa12.5kPa-100kPa250kPa25MPa
1MPa50kPa-100kPa1MPa25MPa
3MPa150kPa-0.1MPa3MPa25MPa
10MPa500kPa-0.1MPa10MPa25MPa
40MPa5MPa-0.1MPa40MPa42MPa


Performance parameters

Performance testing standards and benchmark conditions

Test standards: In accordance with GB/T28474 and IEC60770;

Reference conditions: zero-range, silicone oil-filled, 316L stainless steel isolation diaphragm,analog signal output, end-base fine-tuning to the set value. This process complies with theverification procedure of pressure transmitters and can provide the corresponding technical standardcertificates.


Performance indicators

Overall performance includes but is not limited to the combined errors of [reference accuracy],[environmental temperature influence], and other factors.

Typical accuracy: 0.075% of full scale

Annual stability: 0.2% of full scale per 5 years


Reference accuracy

Calibration is based on standard and benchmark test conditions, includinglinearity, hysteresis and repeatability.

Calibration temperature: 20C 5C

TD≤10; ±0.075% of full scale10<TD10(0.001 Xupper

10<TD ≤10 ±(0.001 × upper limit of TD range)%

(TD refers to the range ratio)


Material indicators

Liquid contact parts:316L stainless steel

Non-contacting part:

Shell: 316L stainless steel

Hermes connector: PA

O-ring: Nitrile rubber

Flat gasket: Special-shaped fluororubber

Internal pressure transmission medium: Silicone oi


Electrical performance indicators

Signal type4-20mARS 485
Power supply voltage12-30VDC12-30VDC
Load current≤60mA≤45mA
Load resistance<(U-12)/0.06≥5KΩ
Transmission distance<1000 meters<1200 meters
power≤1.5W≤1.1W


Service Guarantee
Service Guarantee
Service Content
Noncon Instrument provides comprehensive pre-sales and after-sales services, including product selection guidance, on-site technical support, installation guidance, and product quality assurance based on customer needs. The company promises a maximum product quality assurance period of 24 months and lifetime free product calibration services to ensure maximum customer benefits.
Product Inquiry
Product Name:
Contact Sales
There are currently no sales available in this region
成都市
成都市

Regional ManagerManager Peng

Contact number86-18030837175

杭州市
杭州市

Regional ManagerManager Zeng

Contact number86-18520508508

西安市
西安市

Regional ManagerManager Jiang

Contact number86-13324545911

武汉市
武汉市

Regional ManagerManager Gao

Contact number86-13871508295

广州市
广州市

Regional ManagerManager Yuan

Contact number86-13711120640

High performance industrial automation instruments
Provide customers with the necessary solutions, intelligent instruments and meters, and achieve sustainability and business goals.