UF 200 is a full function handle transfer time ultrasonicDAAAflow meter. No matter you want to quickly verify theflow reading of another meter or to data log flowD网网system values over an extended time period, theVoxtmeter UF200 is the suitable tool. The UF200portable meter has the clamp on transducers notapping or cutting is required,just clamp outside ofthe pipe. The meter can be easily moved andinstalled in different pipe and convenient to carry site to site.Its portability makes itan excellent choice formeasuring flows throughout the plumbing infrastructure toverify sensor, pump andvalve performance.
1. Easy to install, reduced installation time and cost.
2. No pressure head loss, No moving parts tomaintain or replace.
3. BTU function is an option. UF200 could be used asa portable ultrasonic energy meter.
4. Powerful data storage and also support the datasheet analysis software.
UF 200 ultrasonic flowmeter widely application in oil industry, water treatment, purewater, chemical and etc.
| Performance specifications | |
| Flow range | ±0.03 ft/s ~ ±40 ft/s (±0.01 m/s~±12 m/s) |
| Accuracy | ±1% of measured value |
| Pipe size | Clamp-on:1"~48" (25mm~1200mm) |
| Fluid | Single medium liquid |
| Pipe material | Carbon steel,stainless steel,PVC and other compact material pipe |
| Function specifications | |
| Outputs | Analog output: 4~20mA, Max 750 ΩModbus: RS485 |
| SD card | 16G |
| Interval | 1 ~ 99999seconds |
| Key broad | Digital keys |
| Display | 240*128 back lit LCD |
| Power supply | Rechargeable Lithium Battery Power, 3000mAh(Continuous operation of main battery 16 hours). |
| Temperature | Transmitter: -40℃~60℃ Transducer: -40℃~80℃ (-40℃~80℃ is standard; -40℃~130℃ is an option) |
| Humidity | Up to 99% RH,non-condensing |
| Physical specifications | |
| Transmitter | NEMA13,IP54. |
| Transducer | Encapsulated design,IP68 |
| Transducer cable | Standard cable length: 5m (16ft). |


Accessories
1. carrying case *1pc 2. Transmitter (Electronic)*1pc. 3. Transducer (Sensor) *1 pair.
4. Mounting track*1 set, ST or DT 5. Pipe straps *2 pairs.
6. Coupling compound (Grease)*1 pc, Battery charge*1pc, Output cable*1pc and Tapeline*1
The first condition for ultrasonic flow meter is the pipe must be full of liquid, the bubbles will greatly influence the accuracy of the measurement, please avoid thefollow installation position:

The suggestion installation area is as following:

A is for upright pipeline, please notice the water direction is from the bottom to top.
B is for horizontal pipeline, the transducers need to be installed inside the C area,angle for area C, max120°.
We suggest avoiding the valve, T-brancpipe and elbows if the condition allow.Please satisfied the hardest positioninstallation requirements when you facemore than one interfering resource.

Transfer time technical means the ultrasonic signal from the transducer istransmitted and received through the moving liquid, there will be a differencebetween the upstream and downstream transit time, which can be used tocalculate flow and velocity.