The FX-102 type steam thermal energy accumulation meter is an instrument based on ARMmicroprocessor, which works in conjunction with various flow transmitters and sensors to measure flow andcomplete the thermal energy measurement of steam heat carrier.
It collects, displays, controls, transmits remotely, communicates and prints various signals such as on-site temperature and flow rate, forming a digital acquisition system and control system. It is particularlysuitable for trade settlement and measurement management, and realizes online measurement of heattransfer, thereby providing a basis for enterprise energy management, energy consumption measurement andtechnical economy.
It is applicable to a wide range of flowmeters
Automatic conversion of flow units and automatic calculation of the flow coefficient fordifferential pressure flowmeters.
Trade settlement function: Protocol settlement can be enabled for high/low flow.
Emergency fault-tolerant function: When the temperature and pressure signals are abnormal, theemergency parameter values are used for compensation calculation.
Debugging and calculation function: Supports viewing the original values of signals from each transmitter/sensor, supports viewing various intermediate parameters in flow and heat energy caloulation, such as densityand enthalpy value, etc.
Audit record: Power outage record.
Alarm list: Supports recording alarm information of instantaneous or cumulative values such as flow,thermal energy, temperature, pressure, differential pressure/frequency/volume,etc.
Cumulative reports: Support daily, monthly and annual reports of cumulative flow and heat energy.
Communication function: Standard Modbus RTU protocol, supporting RS485 and RS232Ccommunication interfaces.
Display
| Screen | 128×64 dot matrix monochrome liquid crystal display (LCD) |
| Precision | Display and measurement accuracy: ±0.2% F.S. |
| Memory recall accuracy | ±0.2% F.S. |
| Instantaneous flow rate units | m³/h, m³/min, m³/s, L/h, L/min, L/s, t/h, t/min, t/s, kg/h, kg/min, kg/s, km³/h, Nm³/h, kNm³/h |
| Instantaneous heat units | kJ/h, MJ/h, GJ/h, kCal/h, MCal/h, GCal/h, W, kW, MW, GW |
Processor
| Adopting a high-performance 32-bit RISC core of ARM Cortex-M3 |
Input function
| Flow channel | Analog signals: 4-20mA, 0-10mA, etc.; |
| Frequency signal | Fr (range: 0.0 - 5000.0 Hz, low level ≤ 1V, high level ≥ 5V); |
| Temperature channel | 0-10mA, 4-20mA, Pt100, etc. signals |
| Pressure channel | 0-10mA, 4-20mA and other signals |
| Note: Other input signals (such as digital input (DI)) should be specified at the time of ordering. | |
Output function
| Power distribution output | Provides 1 group (F12) of 12VDC and 2 groups (Q24, P24) of 24VDC sensor power supply. Maximum output current per channel: 30mA. The 24V power distribution for flow current Q24 and the 24V power distribution for pressure P24 share a common ground. |
| Transmitter output | Supports 1 channel of standard current transmitter output (source selectable), with a maximum load capacity of 500Ω. |
| Relay output | Supports 2-channel relay output, configurable for upper-upper limit, upper limit, lower limit, and lower-lower limit alarms. Contact capacity: 3A @ 250VAC / 3A @ 30VDC |
Communication function
| Communication interface | Two communication interfaces, RS232C and RS485, are provided for users to choose from, and both are supported. Supports Modbus RTU protocol, baud rate: 1200, 2400, 4800, 9600 |
| Printing interface | RS232C directly connects to a micro printer, with a baud rate of 1200 |